16-Oct-2026 – The Government of Alberta released updated STANDATA variance 23-BCV-011R1 which provides a valuable working solution to many greenhouses and garden retailers in the province.
The Alberta Greenhouse Growers Association (AGGA) worked with the Municipal Affairs in support of amending this variance to allow a working solution to publicly accessible greenhouse spaces whilst respecting safety and fire codes.
- For non-public greenhouses: no flame resistance requirement if film’s flame spread rating does not exceed 25
- For public-access greenhouses: similar flame spread limit, plus restrictions on building height, occupancy, aisle width, exit sizes, occupant load calculations, signage, and fire safety planning. A full summary of these requirements are listed below.
- The greenhouse is one storey in building height and primarily used for the growing, display, and retail sale of plants (flowers, vegetables, shrubs, trees, and similar horticultural products)
- The building is classified as a Group F, Division 3 major occupancy (low-hazard industrial occupancy);
- Public access is limited to retail activities directly related to the sale of plants and horticultural products;
- The polyethylene film is not required to conform to CAN/ULC-S109, “Standard Method for Flame Tests of Flame-Resistant Fabrics,” if it has a flame spread rating not exceeding 25;
- Public access aisles have a clear width of not less than 1.1 m and be arranged to provide access to exits in at least two directions of travel, with no dead-end aisles;
- Exit doors serving publicly accessible areas are increased in width by not less than 40% above the minimum width required by the NBC(AE) but not less than 1190 mm;
- Occupant load is calculated using 4.6 m² per person for areas accessible to the public;
- Every exit door is provided with exit signage in accordance with the NBC(AE);
- Spatial separation and exposure protection comply with the NBC(AE). Where more than one greenhouse is located on the same property, the spatial separation between greenhouses may be determined in accordance with the provisions applicable to tents and air-supported structures (Subsection 3.1.18.); and
- A Fire Safety Plan must be prepared, implemented, and maintained in accordance with the National Fire Code – 2023 Alberta Edition. The Fire Safety Plan must address emergency procedures, evacuation procedures, staff responsibilities, fire protection and life safety systems, maintenance requirements, and emergency contact information. Where required by the building or fire authority having jurisdiction, the Fire Safety Plan must be submitted for review and approval prior to occupancy.
The full document and details can be found at 23-BCV-011R1 Polyethylene film for greenhouse enclosures. AGGA are working with a fire code consultant to develop a templated fire safety plan for publicly accessible greenhouses. This template will act as a starting point for growers to develop their own plans in consultation with local building and fire codes inspectors.
This updated policy provides a clear path for greenhouse operators with existing structures and those looking to build new structures that will comply with local, provincial and federal building codes.
If you have questions or require clarification on any point, please send an email to member_services@agga.ca